Mv display for heating and cooling control, In-t – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 133

Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation
3-63
EXAMPLE
When the PV/SP Display Screen Parameter Is Set to 2
Figure 3.134
MV Display for Heating and
Cooling Control
Select either the manipulated variable (heating) or manipulated variable
(cooling) as the MV to be displayed for PV/SP/MV during heating and
cooling control. The MV Display Selection parameter is displayed only when:
1.
heating/cooling control is being performed and PV/SP/MV is selected
in the PV/SP Display Screen parameter
or
2.
a Monitor/Setting Item Display parameter.
EXAMPLE
PV/SP/MV and PV/SP/Multi-SP on the Process Value/Set Point Display
This procedure displays PV/SP/MV and PV/SP/Multi-SP on the Process
Value/Set Point display. The PV/SP Display Screen Selection parameter is set
to 2.
1.
Press the
O Key for at least three seconds to move from the Operation
function group to the Initial Setting function group.
Figure 3.135
25
100
50.0
25
100
sp0
Press the
M
key
PV/SP/MV
PV/SP/Multi-SP
Operation Function Group
PV/SP (Display 1)
C
C
PV/SP (Display 2)
Table 3.R
Parameter Name
Set Value Symbol Display Contents
MV Display
Selection
O
o
Manipulated variable (heating)
C-O
c-o
Manipulated variable (cooling)
C
25
100
PV/SP
Input Type
in-t
5