Publication 900-UM007D-EN-E - January 2011

Calibration

C-7

Figure C.6 — Example, Zero Controller

3. Turn the power ON.

4. Move to the Calibration function group. This starts the 30-minute timer.

This timer provides an approximate timer for aging. After 30 minutes,
the No. 2 display changes to 0. You can advance to the next step in this
procedure even if 0 is not displayed.

Figure C.7

5. Press the M key to set the Bulletin 900 Controller to the state below.

The No. 2 display at this time displays the currently entered count value
entered in Hexadecimal. Set the STV as follows:

• Input Types 5, 7, 11, 12, 15: Set to 54 mV.
• Input Types 6, 8, 9, 10, 13, 14, 16, 17, 18, 19, 20, 21, 22, 24, 25: Set to

24 mV.

Figure C.8

Allow the count value on the No. 2 display to fully stabilize, then press
the

D key to temporarily register the calibration setup. If the count

Leave Open

900-TC8
900-TC16
900-TC32

Zero

Controller

STV

DMM

19/4/11

20/5/12

+

OUTPUT

INPUT

Compensating conductor of currently
selected thermocouple.
Use the K thermocouple compensating
conductor for:

• E, R, S, B, W, and PLII thermocouples and
• the non-contact temperature sensor

adj

30

Input Types
6, 8, 9, 10, 13,
14, 16, 17, 18,
19, 20, 21, 22:

t

-

24

e220

t

-

54

b9a5

Input Types
5, 7, 11, 12, 15: