Dead band (heating and cooling control) – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 149

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-13

Dead Band (Heating and Cooling Control)

When the heating and cooling control mode is selected, the Dead Band
parameter can be used. The dead band is configured with the set point as its
center (refer to Figure 4.26). The dead band width is the configured value of
the Dead Band parameter (Adjustment function group). Setting a negative
value produces an overlap band. If an overlap band is configured the bumpless
function may not operate when switching between automatic and manual
operation.

Note: The default is 0.0 EU for controllers with temperature inputs and

0.00% full scale for controllers with analog inputs.

Table 4.C — Example: 900-TC8 & 900-TC16

Parameter Name Symbol

Without Control Output 2

With Control Output 2

Standard

Heating/Cooling

Standard

Heating/Cooling

Control Output 1
Assignment

out1

Control Output
(heating)

Control Output
(heating)

Control Output
(heating)

Control Output
(heating)

Control Output 2
Assignment

out2

Not assigned

Not assigned

Not assigned

Not assigned

Auxiliary Output 1
Assignment

sub1

Alarm 1

Alarm 1

Alarm 1

Alarm 1

Auxiliary Output 2
Assignment

sub2

Alarm 2

Control Output
(cooling)

Alarm 2

Alarm 2

➊No parameter assignment is displayed because there is no control output

➋The output set for the Auxiliary Output 1 Assignment parameter becomes the program END output unless the program pattern is OFF.

➌ For the 900-TC8, the Auxiliary Output 3 Assignment parameter is set for control output (cooling) (the Auxiliary Output 2 Assignment parameter is set for alarm 2).

• The heating/cooling operation of the control outputs will switch when the Direct/Reverse Operation parameter is set to “direct.”
• When DRS (Invert Direct/Reverse Operation) is assigned for an Event Input Assignment (1 or 2), control will start with the contents set for the Direct/Reverse Operation

parameter inverted when the event input turns ON, and with the contents left according to the setting when the event

input turns OFF. For details on event inputs and control combined with the Direct/Reverse Operation parameter, refer to Control by Inverting Direct/ Reverse Operation.

This function is not supported by 900-TC32.

• When heating/cooling control is selected, the Dead Band and Cooling Coefficient parameters can be used.

Table 4.D — Example: 900-TC32

Parameter Name

Symbol

Standard

Heating/Cooling

Control Output 1 Assignment

out1

Control output (heating)

Control output (heating)

Aux1 Output 1 Assignment

sub2

Alarm 1

Control output (cooling)

The Auxiliary Output 1 Assignment parameter becomes the program end output

unless the Program Pattern parameter is configured to OFF.