Page 134: In-t

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

3-64

Configuration & Basic Operation

2.

Press the

M Key to select the Move to Advanced Setting function

group.

Figure 3.136

3.

Use the

D Key to enter the password (“-169”). It is possible to move to

the Advanced Setting function group by either pressing the

M Key or

waiting two seconds without pressing any key.

Figure 3.137

4.

Press the

M Key to select the PV/SP Display Screen Selection

parameter.

Figure 3.138 — PV/SP Display Screen

5.

Use the

U and D Keys to configure the parameter to a value of 2.

Figure 3.139

6.

Press the

O Key for at least one second to move from the Advanced

Setting function group to the Initial Setting function group.

Figure 3.140

7.

Press the

O Key for at least one second to move from the Initial

Setting function group to the Operation function group. The MV will
be displayed on the No. 3 display.

Figure 3.141

amov

-169

Move to
Advanced
Function Setting
Level

Parameter
Initialization

init

off

spdp

4

PV/SP Display
Screen Selection

spdp

2

in-t

5

Input Type

25

100

50.0

PV/SP

C