Using the transfer output, Transfer output function – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 198

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-62

Parameter Adjustments & Application Considerations

Using the Transfer Output

Transfer Output Function

Fort 900-TC8 and 900-TC16, if a control 1 output is an analog linear current
output it can be used as a transfer output. To use the transfer output, configure
the Transfer Output Type parameter to any setting other than OFF (refer to
Table 4.AE).
When the Transfer Output Type parameter is configured to any setting other
than OFF, the Transfer Output Upper-Limit and Transfer Output
Lower-Limit parameters will be enabled.

Transfer Output Type

➊ The default Transfer Output Type is OFF. If the Transfer Output Type is configured to OFF, the function assigned

in the Control Output 1 Assignment parameter will be output to Control Output 1.

➋ The difference between the transfer output value and the linear current output value is illustrated in the

following example and Figure 4.135.
If the linear output is used as the transfer output when the linear current output type is configured to 4…20
mA, 4.0 mA will be output for 0% and 20.0 mA will be output for 100%.
When a linear output is used for the control output, 3.7 mA is output for 0% and 20.3 mA is output for 100%
when the control output for heating is selected to ensure that the control object is controlled at 0% and 100%.

Figure 4.135 —

When the Linear Current Output Type is Set to 4 to 20 mA

Table 4.AE — Using Transfer Input

Transfer Output Type

Symbol

Configurable Range

OFF

off

Set Point

sp

SP Lower-Limit to SP Upper-Limit

Set Point during SP
ramp

sp-m

SP Lower-Limit to SP Upper-Limit

PV

pv

Sensor setting range Lower-Limit to
Sensor setting range Upper-Limit or
Scaling Lower-Limit to Scaling
Upper-Limit

MV Monitor (heating)

mv

–5.0…105.0 (heating/cooling control:
0.0…105.0)

MV Monitor (cooling)

c-mv

0.0…105.0

20.3
20

4
3.7

0

100

Output current (mA)

Transfer output value
Control output

MV (%)

Advertising