Publication 900-UM007D-EN-E - January 2011

5-4

Parameter Functions & Definitions

Initial Setting/Communications Protection

This portion of the Protect function group restricts movement by keypad to
the Initial Setting function group, Communications Setting function group,
and Advanced Setting function group.

Setting/Configuration Change Protection

Conditions of Use:

Event Input Assignment 1 and 2 must NOT be

configured to “Setting Change Enabled/Disabled”

Function:

This portion of the Protect function group restricts changes to

controller setup parameters by key operation.

➋ Default

Note:

The all protect indicator

will light when configuration change

protection is ON.

Table 5.B — Initial Setting/Communications Protection

Configured
Value

Initial Setting
Function Group

Communications Setting
Function Group

Advanced Setting
Function Group

0

1

X

2

X

X

X

➊ Default. Level of Protection: Able to reach, X Cannot reach.

Table 5.C — Setting/Configuration Change Protection

Configurable Range

Default

on: Enabled, off: Disabled

on

Table 5.D — Configuration Change Protection

Configured Value

Description

OFF

Setup can be changed by key operation.

ON

Setup cannot be changed by key operation. (The Protect function
group can be changed.)

icpt