Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 256

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-28

Parameter Functions & Definitions

Note:

If the Heater burnout or heater overcurrent fault is less than or equal to
100 ms it is not detected.

ffff

is displayed when 55.0 A is exceeded.

• If a heater burnout detection 2 or heater overcurrent detection 2 alarm

is output, the HA indicator will light and the No. 1 display for the heater
current 2 value monitor will flash.

Related Parameters

• Heater Burnout Detection 1, Heater Burnout Detection 2 (Adjustment

function group, page 5-30)

• HB ON/OFF (Advanced Setting function group, page 5-74)
• Heater overcurrent detection 1, Heater overcurrent detection 2

(Adjustment function group, page 5-30)

• Heater overcurrent use (Advanced Setting function group, page 5-99)
• Error Displays ct2: (page 5-30)

Leakage Current 1 Monitor (900-TC8, 900-TC16)

Conditions of Use:

Heater Burnout, (HBA) Heater Short (HSA) and Heater

Overcurrent detection must be supported. Alarm 1 must be assigned. The HS
Alarm parameter must be set to ON.

Function:

This parameter measures the heater current from a single CT input

used for detecting a short-circuit condition.

This parameter measures and displays the heater current when the heater is
directed to be OFF by the controller.

Note:

A Heater Short (HS) fault condition is not detected if its duration is 100
ms or less.

Table 5.AC

Monitoring Range

Units

0.0…55.0

A (Amps)

lcr1