Ol-h ol-l, Mv upper-limit – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 270

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-42

Parameter Functions & Definitions

Related Parameters

• Input Type (page 5-50), Scaling Upper-Limit, Scaling Lower-Limit (page

5-52), Decimal Point, ST (page 5-56) (Initial Setting function group)

• SP Ramp Time Units (Advanced Setting function group, page 5-71)

MV (Manipulated Variable) Upper-Limit,

MV (Manipulated Variable) Lower-Limit

Conditions of Use:

The control method must be 2-PID control, and the ST

parameter must be set to OFF.

Function:

The MV Upper-Limit and MV Lower-Limit parameters allow you

to configure the Upper- and Lower-Limits allowed for the manipulated
variable. If the current manipulated variable calculated by the Bulletin 900
Controller exceeds your configured MV upper- or Lower-Limit value, then the
current value becomes the upper or Lower-Limit MV value. Your configured
MV limits will NOT be exceeded by the controller.

MV Upper-Limit

The configurable ranges allowed during the standard control and heating and
cooling control modes are different.

The manipulated variable at the cooling Control Output side during heating
and cooling control is expressed as a positive value (refer to Table 5.AW).

Table 5.AV

Parameter

Configurable Range

Units

Default Value

SP Ramp Value

OFF, 1…9999

EU

OFF

Table 5.AW

Control Mode

Configurable Range

Units

Default Value

Standard

MV Lower-Limit
+0.1…105.0

%

105.0

Heating and cooling

0.0…105.0

%

105.0

ol-h
ol-l

Advertising