Page 299: Sp ramp time units

Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions
5-71
Parameter Initialize
Function:
This parameter allows you to return/reset all of the controller’s
parameter settings to their initial/default values.
Multi-SP Uses
Conditions of Use:
The controller must NOT have an event input option
unit installed or the Number of Multi-SP Uses parameter must be set to 0.
Function:
This parameter allows you to configure the controller for multi-SP
selection (0…3) by operating the keys (
D
U
) on the front of the controller.
If the option event input unit is mounted in the Bulletin 900 controller, this
parameter can be used only when the Number of Multi-SP Uses parameter is
set to 0 and Multi-SP Uses parameter is set to ON.
•
on
: You can select set points 0…3 from the controller’s keypad.
•
off
: You CANNOT select set points 0…3 from the controller’s
keypad.
Note:
The default:
off
Related Parameters
• Multi-SP Set Point Setting (Operation function group, page 5-10)
• Number of Multi-SP Uses (Initial Setting function group, page 5-65)
SP Ramp Time Units
Conditions of Use:
The ST (Self-Tuning) parameter must be set to OFF.
Function:
This parameter allows you to configure the time units for the rate
of change during a SP ramp operation which you previously enabled by
entering a value in the SP Ramp Set Value parameter (Adjustment function
group).
Table 5.CE
Parameter Selection
Default
off: Initialization is not executed.
off
fact: Initializes to the factory settings described in the manual.
init
mspu
spru