Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-83

Note:

1. When AT cancel is specified, it means that AT is cancelled regardless of

whether the AT currently being executed is 100% AT or 40% AT.

2. Alarms 1 to 3, heater burnout, HS alarms, and heater over-current

latches are cancelled.

3. For details on auto/manual operations using the PF Key, refer

Performing Manual Control.

4. Pressing the PF Key for at least one second executes operation

according to the configured value. When the Monitor/Setting Item
parameter is selected, however, the display is changed in order from
Monitor/Setting Item 1 to 5 each time the key is pressed.

5. This function is enabled when PF Key Protect is OFF.

Monitor/Setting Item

Monitor/Setting Item

Setting the PF Setting parameter to the Monitor/Setting function makes it
possible to display monitor/setting items using the function key. The following

LAT

lat

Alarm Latch Cancel Specifies canceling all alarm

latches (see note 2)

A-M

a-m

Auto/Manual

Specifies reversing the
Auto/Manual status (see note 3)

PFDP

pfdp

Monitor/Setting
Item

Specifies the monitor/setting item
display. Select the monitor setting
item according to the Monitor/
Setting Item 1 to 5 parameters
(advanced setting function group).

Table 4.AL

Set Value Symbol Operation

Function

Monitor/Setting Item 1

pfd5

0

Item 5

pfd1

1