In-t, Init, Amov – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 128

Publication 900-UM007D-EN-E - January 2011
3-58
Configuration & Basic Operation
HS Alarm Setup
To activate the HS alarm, set the HS Alarm Use parameter to ON in the
Advanced Setting function group and set the HS Alarm 1 and HS Alarm 2
parameters in the Adjustment function group.
EXAMPLE
Operating Procedure: Moving to the Advanced Setting Function Group
The HS Alarm Use parameter setting is already ON by default, so set the HS
Alarm 1 parameter to 2.5.
1.
Move to the Advanced Setting function group.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 3.116
2.
Select Move to Advanced Setting function group by pressing the
M key.
Figure 3.117
3.
Press the
D key to enter the password (−169), and move from the
Initial Setting function group to the Advanced Setting function group.
The top parameter in the Advanced Setting function group is displayed.
Figure 3.118
4.
Select the HS Alarm Use parameter by pressing the
M key.
Check that this parameter is set to ON (the default).
Next, set the Leakage Current 1 Monitor parameter.
Figure 3.119
C
25
100
PV/SP
in-t
5
Input type
init
off
amov
-169
Moves to Advanced
Setting Function Group
hsu
on
HS alarm
use