Publication 900-UM007D-EN-E - January 2011

3-58

Configuration & Basic Operation

HS Alarm Setup

To activate the HS alarm, set the HS Alarm Use parameter to ON in the
Advanced Setting function group and set the HS Alarm 1 and HS Alarm 2
parameters in the Adjustment function group.

EXAMPLE

Operating Procedure: Moving to the Advanced Setting Function Group

The HS Alarm Use parameter setting is already ON by default, so set the HS
Alarm 1 parameter to 2.5.

1.

Move to the Advanced Setting function group.
Press the

O

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 3.116

2.

Select Move to Advanced Setting function group by pressing the

M key.

Figure 3.117

3.

Press the

D key to enter the password (−169), and move from the

Initial Setting function group to the Advanced Setting function group.
The top parameter in the Advanced Setting function group is displayed.

Figure 3.118

4.

Select the HS Alarm Use parameter by pressing the

M key.

Check that this parameter is set to ON (the default).
Next, set the Leakage Current 1 Monitor parameter.

Figure 3.119

C

25

100

PV/SP

in-t

5

Input type

init

off

amov

-169

Moves to Advanced
Setting Function Group

hsu

on

HS alarm
use