Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 365
Advertising

Publication 900-UM007D-EN-E - January 2011
B-5
Table B.C — Initial Setting Function Group
Parameters
Characters
Setting (Monitor) Value
Display
Default
Unit
Set Value
SP Lower-Limit
sl-l
Input range Lower-Limit to SP
Upper-Limit
− 1 (temperature)
−200
EU
Scaling Lower-Limit to SP Upper-Limit
− 1 (analog)
0
PID ON/OFF
intl
ON/OFF 2-PID
onof
pid
ON/OFF
None
Standard or
Heating/Cooling
s-hc
Standard or heating/cooling
send
h-c
Standard
None
ST
st
OFF, ON
off on
ON
None
Program Pattern
ptrn
OFF, STOP, CONT
off
stop
cont
OFF
None
Control Period
(Heating)
cp
0.5 or 1…99
0.5
1 to 99
20
Second
Control Period (Cooling)
c-cp
0.5 or 1…99
0.5
1 to 99
20
Second
Direct/Reverse
Operation
orev
Reverse operation, direct operation
or-r
or-d
Reverse
operation
None