Publication 900-UM007D-EN-E - January 2011

5-58

Parameter Functions & Definitions

Table 5.BP

• When the standard control mode is selected, use the Control Period

(cool) parameter. The Control Period (heat) parameter cannot be used.

• When the heating control output is an analog output the control period

cannot be used.

• When the heating and cooling control mode is selected, the Control

Period can be configured independently for the heating and cooling
outputs. Use the Control Period (heat) parameter to set the Control
Output 1 side control period, and use the Control Period (cool)
parameter to set the cooling control period.

Related Parameter

• PID ON/OFF (Initial Setting function group, page 5-55)

Direct/Reverse Operation

Function:

This parameter allows you to configure the controller for the direct

or reverse operation of the manipulated variable (MV). Direct operation refers
to the control method where the manipulated variable is increased according
to the increase in the process value. Alternatively, reverse operation refers to
the control method where the manipulated variable is increased according to
the decrease in the process value.

Parameter

Configurable Range

Units

Default Value

Control Period (heat)

0.5 or 1…99

Seconds

20

Control Period (cool)

0.5 or 1…99

Seconds

20

Table 5.BQ

Selections

Default

or-r: Reverse operation, or-d: Direct operation

or-r

orev