Orev, Direct/reverse operation – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 286

Publication 900-UM007D-EN-E - January 2011
5-58
Parameter Functions & Definitions
Table 5.BP
• When the standard control mode is selected, use the Control Period
(cool) parameter. The Control Period (heat) parameter cannot be used.
• When the heating control output is an analog output the control period
cannot be used.
• When the heating and cooling control mode is selected, the Control
Period can be configured independently for the heating and cooling
outputs. Use the Control Period (heat) parameter to set the Control
Output 1 side control period, and use the Control Period (cool)
parameter to set the cooling control period.
Related Parameter
• PID ON/OFF (Initial Setting function group, page 5-55)
Direct/Reverse Operation
Function:
This parameter allows you to configure the controller for the direct
or reverse operation of the manipulated variable (MV). Direct operation refers
to the control method where the manipulated variable is increased according
to the increase in the process value. Alternatively, reverse operation refers to
the control method where the manipulated variable is increased according to
the decrease in the process value.
Parameter
Configurable Range
Units
Default Value
Control Period (heat)
0.5 or 1…99
Seconds
20
Control Period (cool)
0.5 or 1…99
Seconds
20
Table 5.BQ
Selections
Default
or-r: Reverse operation, or-d: Direct operation
or-r
orev