Multi-sp, Selecting multi-sp by keypad operation – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 155

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-19

Multi-SP

Selecting Multi-SP by Event Input

Multi-SP by event input is a function for setting the value of set points 0…3 in
advance, and selecting these set points by a combination of Event Inputs 1 and
2.

Multi-SP selection from external (event) inputs can be used when the proper
option event input unit is mounted in the Bulletin 900 and the Number of
Multi-SP Uses parameter is set to 1 or 2 (refer to Tables 4.G and 4.H).

Note: In order for the controller to begin the multi-set point function, the

physical input must be ON for 50 ms minimum.

Selecting Multi-SP by Keypad Operation

You can select Set Points 0…3 from the controller keypad by properly
configuring the value of the Multi-SP Uses parameter. in the adjustment
function group.To change set points from the controller keypad, the multi-SP
conditions are as follows.

When the option event input unit is:

• When the option event input unit is NOT mounted in the Bulletin 900,

and Multi-SP is configured to ON.

• When the option event input unit is mounted in the Bulletin 900, the

Number of Multi-SP Uses parameter is configured to 0 and the
Multi-SP parameter is configured to ON.

Table 4.G — When Number of Multi-SP Uses Parameter is Set to 1

Event Input 1

Selected Set Point

OFF

Use Set Point 0

ON

Use Set Point 1

Table 4.H —When Number of Multi-SP Uses Parameter is Set to 2

Event Input 1

Event Input 2

Selected Set Point

OFF

OFF

Use Set Point 0

ON

OFF

Use Set Point 1

OFF

ON

Use Set Point 2

ON

ON

Use Set Point 3