Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-91

Function:

This parameter allows you to configure the SP and PV process

condition for the LBA Level parameter.

• If the deviation between the SP and PV exceeds the LBA Level, a

control loop error is detected.

Related Parameters

• Process Value/Set Point (Operation function group, page 5-8)
• Alarm 1 Type (Initial Setting function group, page 5-59)
• LBA Detection Time (page 5-90), LBA Band (page 5-91) (Advanced

Setting function group)

Loop Break Alarm (LBA) Band

Conditions of Use:

Alarm 1 must be assigned. The Alarm Type parameter

must be set to 12 (LBA). The LBA Detection Time must NOT be 0.

Function:

This parameter allows you to configure the LBA band.

• If a control deviation greater than the LBA Band is not reduced when

the LBA Level is exceeded, a control loop error is detected.

Note:

For more details concerning the LBA Band, refer to Section 4,

Loop

Break Alarm on page 4-47.

Table 5.DI

Controller Models

Configurable
Range

Units

Default

Controllers with Thermocouple and
Resistance Thermometer (RTD) Inputs

0.1…999.9

°C or °F ➊

8.0

Controllers with Analog Inputs

0.01…99.99

%FS

10.00

Set NONE as the unit for Controllers with 0… 50 Millivolt Inputs.

Table 5.DJ

Controller Models

Configurable
Range

Units

Default

Controllers with Thermocouple and
Resistance Thermometer (RTD) Inputs

0.0…999.9

°C or °F ➊

3.0

Controllers with Analog Inputs

0.00…99.99

%FS

0.20

Set NONE as the unit for Controllers with 0… 50 Millivolt Inputs.