Parameter Adjustments & Application Considerations
4-11
EXAMPLE
Operation Procedure
In this example, configure the scaling upper- and Lower-Limits so that inputs
4…20 mA become 10.0%…95.0%.
1. Press the
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.19
2. Select Scaling Upper-Limit by pressing
M
.
Figure 4.20
3. Press the
U
or
D
key to set the parameter to 950.
Figure 4.21
4. Select Scaling Lower-Limit by pressing
M
.
Figure 4.22
5. Press the
U
or
D
key to set the parameter to 100.
Figure 4.23
in-t
0
Input type
in-h
100
Scaling upper
limit
in-h
950
in-l
0
Scaling lower
limit
in-l
100