Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-11

EXAMPLE

Operation Procedure

In this example, configure the scaling upper- and Lower-Limits so that inputs
4…20 mA become 10.0%…95.0%.

1. Press the

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.19

2. Select Scaling Upper-Limit by pressing

M

.

Figure 4.20

3. Press the

U

or

D

key to set the parameter to 950.

Figure 4.21

4. Select Scaling Lower-Limit by pressing

M

.

Figure 4.22

5. Press the

U

or

D

key to set the parameter to 100.

Figure 4.23

in-t

0

Input type

in-h

100

Scaling upper
limit

in-h

950

in-l

0

Scaling lower
limit

in-l

100