Publication 900-UM007D-EN-E - January 2011

3-38

Configuration & Basic Operation

Figure 3.72 — Executing AT or ST in RT Mode

• When the manipulated variable (MV) is saturated, the amount of

overshooting may be somewhat higher in comparison to PID control
based on AT or ST in normal mode.

EXAMPLE

Operation Procedure

This example selects RT mode.

1.

Press the

O

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 3.73

2.

Select the Move to Advanced Setting function group parameter by
pressing the

M key.

Figure 3.74

3.

Use the

D key to enter −169 (the password).

It is possible to move to the Advanced Setting function group by
pressing the

M

key or leaving the setting for at least 2 seconds.

Figure 3.75

Temperature

Temperature

Set point value

Set point value

Start of control

Start of control

Time

Time

Improved with RT

C

25

100

PV/SP

in-t

5

Input type

amov

0

Move to Advanced
Setting Function Group

init

off

Parameter
initialization