Out2 sub1, Auxiliary output 1 assignment – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 321

Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions
5-93
Control Output 2 Assignment (900-TC8 &
900-TC16)
Conditions of Use:
Control Output 2 must be assigned/available. For a list of
controllers or option units that provide Control Output 2 functionality refer to
Tables 1.B and 1.E.
Function:
This parameter sets the function to be assigned to Control
Output 2.
Related Parameters
• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
(Initial Setting function group)
Auxiliary Output 1 Assignment
Conditions of Use:
Auxiliary Output 1 must be assigned.
Function:
This parameter allows you to configure the function assigned to
Auxiliary Output 1.
Table 5.DL
Control Output 2 Function
Default
none:
No function is assigned to control output 2
none ➌
o:
Heating control output is output
c-o:
Cooling control output is output
➊
alm1:
Alarm 1 is output
alm2:
Alarm 2 is output
alm3:
Alarm 3 is output
p.end:
Program end is output
➋
ralm:
Control output ON/OFF count alarm
➊ If
c-o
is assigned for standard control, a value equivalent to 0% will be output.
➋ Can be selected only when the program pattern is not set to OFF, but the function is disabled.
➌ If the Standard or Heating/Cooling parameter is set to heating/cooling control, control automatically switches
to
c-o
.
out2
sub1