Out2 sub1, Auxiliary output 1 assignment – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 321

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-93

Control Output 2 Assignment (900-TC8 &

900-TC16)

Conditions of Use:

Control Output 2 must be assigned/available. For a list of

controllers or option units that provide Control Output 2 functionality refer to
Tables 1.B and 1.E.

Function:

This parameter sets the function to be assigned to Control

Output 2.

Related Parameters

• Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),

(Initial Setting function group)

Auxiliary Output 1 Assignment

Conditions of Use:

Auxiliary Output 1 must be assigned.

Function:

This parameter allows you to configure the function assigned to

Auxiliary Output 1.

Table 5.DL

Control Output 2 Function

Default

none:

No function is assigned to control output 2

none ➌

o:

Heating control output is output

c-o:

Cooling control output is output

alm1:

Alarm 1 is output

alm2:

Alarm 2 is output

alm3:

Alarm 3 is output

p.end:

Program end is output

ralm:

Control output ON/OFF count alarm

➊ If

c-o

is assigned for standard control, a value equivalent to 0% will be output.

➋ Can be selected only when the program pattern is not set to OFF, but the function is disabled.

➌ If the Standard or Heating/Cooling parameter is set to heating/cooling control, control automatically switches
to

c-o

.

out2

sub1