Publication 900-UM007D-EN-E - January 2011

Preparations

2-23

(LBA) and Heater Short Alarm (HSA) that are provided for the Bulletin
900 Controller.)

Figure 2.20

Select a surge absorber that satisfies the following conditions.

Control Output 2

• For 900-TC8 & 900-TC16: Output 2 is applied from terminals 11 and

12 or 14 and 15 with the 900-TC16, and from pins 14 and 15 with the
900-TC8. The following diagrams show the available outputs and their
equal internal circuits.

Figure 2.21

➊ Option Unit: 900-TC16P1V2

➋ Option Unit: 900-TC16NCOMV2

The following table shows the specifications for each output type.

Table 2.G

Voltage Used

Varistor Voltage

Surge Resistance

100…120V AC

240…270V

1,000 A min.

200…240V AC

440…470V

Table 2.H — 900-TC8

Output Type

Output 2 Specifications

Triac (AC) relay

250V AC, 3 A (resistive load), electrical durability: 1,000,000
operations

Voltage (PNP)

PNP type, 12V DC +15%/

−20%, 21 mA (with short-circuit

protection)

1

2

Triac (AC)
relay output

Varistor

Varistor

Inductive
load

+

v

L

+

v

L

+

v

L

900-TC8 Control Output 2

Relay

Voltage

GND

Voltage

Voltage

900-TC16 Control Output 2

or

GND

GND