Alsp manl, Alarm sp selection, Manual mv limit enable – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 325

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-97

Function:

This parameter allows you to configure the units of time used for

the soak time when the simple program function is used.

Related Parameters

• Program Start, Soak Time Remain (Operation function group, page

5-15)

• Soak Time, Wait Band (Adjustment function group, page 5-40)
• Program Pattern (Initial Setting function group, page 5-57)

Alarm SP Selection

Conditions of Use:

Alarm 1, 2, and 3 functions must be assigned. The SP

Ramp Set Value must NOT be set to OFF. The ST parameter must be set to
OFF. The Alarm Type parameter must set to 1, 2, 3, 4, 5, 6, or 7.

Function:

This parameter allows you to configure whether the set point that

triggers a deviation alarm during SP ramp operation is the ramp SP or target
SP.

Related Parameters

• SP Ramp Set Value (Adjustment function group, page 5-41)
• ST (Initial Setting function group, page 5-56)

Manual MV Limit Enable

Conditions of Use:

The control must be set to 2-PID control.

Table 5.DQ

Selections

Default

m: Minutes, h: Hours

m

Selections

Default

sp-m: Ramp SP, sp: SP

sp-m

alsp