E333, Ad converter error, Meaning – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 343: Action, Operation, There is an error in internal circuits, The control outputs and alarm outputs turn off, Figure 6.1

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Troubleshooting & Error Indication

6-3

Figure 6.1

AD Converter Error

Meaning

There is an error in internal circuits.

Action

First, turn the controller power OFF then back ON again. If the display
remains the same, the Controller must be repaired. If the display is restored,
then the probable cause is electrical noise affecting the control system. Check
for electrical noise.

Operation

• The control outputs and alarm outputs turn OFF.

Control range

s.err

display

Numeric display

s.err

display

Input indication range

1999

9999

Control range

s.err

display

[[[[

display

Numeric display

Input indication range

]]]]

display

s.err

display

Display range

1999

9999

Control range

s.err

display

Numeric display

s.err

display

Display range

Resistance Thermometer Input
(Except for models with a setting range of −199.9 to 500.0 °C)
Thermocouple Input
(Except for models with a setting range of −199.9 to 400.0 °C)

Control range

s.err

display

[[[[

display

Numeric display

Input indication range

s.err

display

Resistance Thermometer Input
(Except for models with a setting range of −199.9 to 500.0 °C)
Thermocouple Input
(Except for models with a setting range of −199.9 to 400.0 °C)

Analog Input
When Display Range > Control Range

Analog Input
When Display Range < Control Range

1

1

1

The display range is shown in numbers with decimal points omitted.

e333