Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 88

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

3-18

Configuration & Basic Operation

Figure 3.21 — Direct/Reverse Operation

For example, when the process value (PV) temperature is lower than the set
point (SP) temperature in a heating control system, the manipulated variable
(OUT1) increases (ON) by the difference between the PV and SP values.

Accordingly, this becomes reverse operation in a heating control system, or
alternatively, direct operation in a cooling control system.

Direct/reverse operation is set in the Direct/Reverse Operation parameter
(Initial Setting function group).

Note:

The Direct/Reverse Operation parameter default is reverse operation.

EXAMPLE

Operation Procedure

In this example, the Input Type, Temperature Unit, Direct/Reverse Operation,
and Control Period (HEAT) parameters will be monitored.

The setup of parameters is as follows:

Input Type =

5: K thermocouple

Temperature Unit =

c: °C

Direct/Reverse Operation =

or-r: reverse operation

Control Period (HEAT) = 20 seconds

1.

Press the

O

key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

High temperature

Manipulated variable (MV)

Direct operation

Low temperature

Set value (SP)

High temperature

Manipulated variable (MV)

Reverse operation

Low temperature Set value (SP)

100%

0%

100%

0%