Parameter Adjustments & Application Considerations
Figure 4.42
2. Select Set Point Upper-Limit parameter by using the
M
key.
Figure 4.43
3. Press the
U
or
D
key to set the value to 1000.
EXAMPLE
Operation Procedure: Configuring the Set Point Lower-Limit
Configure the Set Point Lower-Limit Value to –100.
1. Select Set Point Lower-Limit parameter in the Initial Setting function
group by using the
M
key.
Figure 4.44
2. Press the
U
or
D
key to set the value to –100.
Figure 4.45
Note: The newly configured value or parameter is loaded into the controller
memory if you do NOT operate any key on the front panel for at least
2 seconds or by pressing the
or
M
key.
in-t
5
Input type
C
sl-h
1300
Set point upper-
limit
C
sl-h
1000
C
sl-l
-200
Set point lower
limit
C
sl-l
-100