In-t, Sl-h, Sl-l – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 164

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-28

Parameter Adjustments & Application Considerations

Figure 4.42

2. Select Set Point Upper-Limit parameter by using the

M

key.

Figure 4.43

3. Press the

U

or

D

key to set the value to 1000.

EXAMPLE

Operation Procedure: Configuring the Set Point Lower-Limit

Configure the Set Point Lower-Limit Value to –100.

1. Select Set Point Lower-Limit parameter in the Initial Setting function

group by using the

M

key.

Figure 4.44

2. Press the

U

or

D

key to set the value to –100.

Figure 4.45

Note: The newly configured value or parameter is loaded into the controller

memory if you do NOT operate any key on the front panel for at least
2 seconds or by pressing the

or

M

key.

in-t

5

Input type

C

sl-h

1300

Set point upper-
limit

C

sl-h

1000

C

sl-l

-200

Set point lower
limit

C

sl-l

-100