Parameter Functions & Definitions

5-65

Number of Multi-SP Uses (900-TC8, 900-TC16)

Conditions of Use:

An event input unit must be assigned. An optional event

input unit must be installed in the controller.

Function:

Multi-SP is a function for setting set points 0 to 3 in advance, and

switching between these set points using a combination of event input
ON/OFF signals. The number of Multi-SP Uses parameter is used to switch
between using two and four preset set points.

Whether the Event Input Assignments 1 and 2 parameters are displayed or
hidden is determined by the Number of Multi-SP Uses parameter setting.

The following tables show the relationships between ON/OFF combinations
of event inputs 1 and 2 and selected set points.:

Table 5.BX

Configurable Range

Default

0 to 2

1

Table 5.BY — Controllers with Event Inputs 1 and 2 (Two Event Inputs)

Event Input Assignment 1

Event Input Assignment 2

Number or
Multi-SP uses

0

Displayed (Multi-SP not used).

1

Hidden (Multi-SP, 2 points)

Displayed (Event input 2 not
used as multi-SP switch).

2

Hidden (Multi-SP, 4 points).

Table 5.BZ —Number of Multi-SP Uses: 1

Event input 1

Selected set point

OFF

Set point 0

ON

Set point 1

Table 5.CA — Number of Multi-SP Uses: 2

Event input 1

Event input 2

Selected set point

OFF

OFF

Set point 0

ON

OFF

Set point 1

OFF

ON

Set point 2

ON

ON

Set point 3