Publication 900-UM007D-EN-E -January 2011

C-12

Calibration

Figure C.20

10. The calibration mode is ended by turning the controller power OFF.

Calibrating Platinum
Resistance Thermometers

This example describes how to calibrate the Bulletin 900 Controller when it is
connected to a platinum resistance thermometer.

Figure C.21

When calibrating a platinum resistance thermometer use wires of the same
thickness as those used to connect the Bulletin 900 Controller.

1. Connect the power supply.

2. Connect a precision resistance box (called 6-dial in this manual) to the

platinum resistance thermometer input terminals.

3. Turn the power ON.

4. Move to the Calibration function group. This starts the 30-minute aging

timer. This timer provides an approximate timer for aging. After
30 minutes, the No. 2 display changes to 0. You can advance to the next
step in this procedure even if 0 is not displayed.

str

no

900-TC8

900-TC16

900-TC32

900-TC16

4

3

5

10

9

A

B'

B

6-dial

Input Power Supply

A

B'

B

6-dial

Input Power Supply

900-TC32

1

2

10

11

12

Input Power Supply

6-dial

1

B

B

A

900-TC8

2

18

19

20