A-m m-sp – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 191

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-55

display the Manual Control function group. It is not possible to move to any
displays except for the PV/MV parameter during manual operation. Press the

O key for at least 1 second from the PV/MV display in the Manual Control
function group to return to automatic mode and display the top parameter in
the Operation function group.

Note: To use the Manual Control mode, the Auto/Manual Select Addition

parameter must first be configured to ON in the Advanced Setting
function group (refer to Figure 4.115 on page 4-57).

Figure 4.110

For 900-TC8 and 900-TC16, if an event input is configured to MANU
(Auto/Manual), the Auto/Manual Switch parameter will not be displayed. Use
the event input to switch between automatic and manual modes.

Note: Even when controller operation is stopped, the manual control of the

MV is given priority over other functions.
Controller auto-tuning and self-tuning will stop when the Manual Mode
is entered.

Note: If the SP ramp function is operating, it will continue even when the

manual mode is entered.

C

M

M

M

C

C

M

a-m

25

25

100

25

20

Press

O

key for at least 1 s.

a-m

m-sp

0

Operation function group

Manual Control function group

PV/MV

Press

O

key for at least

3 s.

a-m

display flashes for

at least 1 s.

PV

PV/SP

Auto/manual switch

Multi-SP