Pf setting – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 329

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-101

Related Parameters

• Heater overcurrent use (Advanced Setting function group, page 5-99)

PF Setting

Conditions of Use:

The PF Key must be supported (900-TC8)

Function:

This parameter allows you to configure which function the PF Key

will have.

Related Parameters

• Monitor/setting item 1 to 5 (Advanced Setting function group, page

5-102)

Table 5.DX

Set Value

Setting

Function

OFF:

off

Disabled

Does not operate as a function key

RUN:

run

RUN

Specifies RUN status.

STOP:

stop

STOP

Specifies STOP status.

R-S:

r-s

Reversing
RUN/STOP
operation

Specifies Reversing RUN/STOP operation status.

AT-2:

at-2

100% AT
Execute/Cancel

Specifies reversing 100% AT Execute/Cancel
status

AT-1:

at-1

40% AT
Execute/Cancel

Specifies reversing 40% AT Execute/Cancel
status

LAT:

lat

Alarm Latch
Cancel

Specifies canceling alarm latches

A-M:

a-m

Auto/Manual

Specifies reversing Auto/Manual status

PFDP:

pfdp

Monitor/Setting
Item

Specifies the monitor/setting item display. Select
the monitor/setting item using the
Monitor/Setting Item 1 to 5 parameters
(Advanced Setting function group).

➊ When AT cancel is specified, it means that AT is cancelled regardless of whether the AT currently being

executed is 100% AT or 40% AT.

➋ Alarms 1 to 3, heater burnout, HS alarms, and heater overcurrent latches are cancelled.

➌ For details on auto/manual operations using the PF Key, refer to Performing Manual Control

pf