Pf setting – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 329

Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions
5-101
Related Parameters
• Heater overcurrent use (Advanced Setting function group, page 5-99)
PF Setting
Conditions of Use:
The PF Key must be supported (900-TC8)
Function:
This parameter allows you to configure which function the PF Key
will have.
Related Parameters
• Monitor/setting item 1 to 5 (Advanced Setting function group, page
5-102)
Table 5.DX
Set Value
Setting
Function
OFF:
off
Disabled
Does not operate as a function key
RUN:
run
RUN
Specifies RUN status.
STOP:
stop
STOP
Specifies STOP status.
R-S:
r-s
Reversing
RUN/STOP
operation
Specifies Reversing RUN/STOP operation status.
AT-2:
at-2
100% AT
Execute/Cancel
Specifies reversing 100% AT Execute/Cancel
status
➊
AT-1:
at-1
40% AT
Execute/Cancel
Specifies reversing 40% AT Execute/Cancel
status
➊
LAT:
lat
Alarm Latch
Cancel
Specifies canceling alarm latches
➋
A-M:
a-m
Auto/Manual
Specifies reversing Auto/Manual status
➌
PFDP:
pfdp
Monitor/Setting
Item
Specifies the monitor/setting item display. Select
the monitor/setting item using the
Monitor/Setting Item 1 to 5 parameters
(Advanced Setting function group).
➊ When AT cancel is specified, it means that AT is cancelled regardless of whether the AT currently being
executed is 100% AT or 40% AT.
➋ Alarms 1 to 3, heater burnout, HS alarms, and heater overcurrent latches are cancelled.
➌ For details on auto/manual operations using the PF Key, refer to Performing Manual Control
pf