In-t, Initial setting function group – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 276

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-48

Parameter Functions & Definitions

(900-TC8) the PV, SP and the Manual MV can be displayed if the third
parameter is enabled (refer to the following graphics displays)

Related Parameters

• Standard or Heating/Cooling (Initial Setting function group, page 5-55)

Initial Setting Function
Group

This function group is for configuring the basic parameters of the Bulletin 900
controller. In this function group, you can configure the Input Type parameter
for selecting the sensor input to be connected to the Bulletin 900 controller,
limit the range of set points, or set the alarm mode, and perform other
operations.

Table 5.BB

Monitor Range

Units

Process value

Temperature: According to indication range for
each sensor.

Analog: Scaling lower limit -5% FS to Scaling
upper limit +5% FS

EU

Set Point

SP lower limit to SP upper limit

EU

Table 5.BC

Configurable Range

Units

MV (manual MV)

Standard control

−5.0…105.0 ➊

%

Heating/cooling control

−105.0…105.0 ➊

When the MV Limit Enable Parameter is configured to ON, the configurable range will be the MV Lower Limit

to MV Upper Limit.

PV/SP/Manual MV

25

100

50.0

MANU

With No. 3 Display

C

25

50.0

MANU

C

Without No. 3 Display

25

MANU

50.0

C

Note: When the PV/SP Display screen selection parameter is 0.

in-t

Advertising