Parameter Adjustments & Application Considerations

4-45

Parameters Related to Alarm Delays

Note: The default time values are 0 (i.e., the ON and OFF delays are disabled).

Note: The parameters are displayed when alarm functions are assigned and

when the alarm type is configured to any type but 0 (none).

EXAMPLE

Operating Procedure

The following example procedure shows how to configure ON and OFF delay
for Alarm Output 1.

An ON delay of 5 seconds and an OFF delay of 10 seconds will be configured.

Figure 4.84

1. Press the O key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.85

2. Select the Move to Advanced Setting function group parameter by

pressing the

M key.

Figure 4.86

Table 4.AA

Parameter Name

Symbol

Configurable Range

Alarm 1 ON delay

a1on

0…999 (s)

Alarm 2 ON delay (900-TC8, 900-TC16)

a2on

0…999 (s)

Alarm 3 ON delay (900-TC8)

a3on

0…999 (s)

Alarm 1 OFF delay

a1of

0…999 (s)

Alarm 2 OFF delay (900-TC8, 900-TC16)

a2of

0…999 (s)

Alarm 3 OFF delay (900-TC8)

a3of

0…999 (s)

C

25

100

PV/SP

in-t

5

Input type