Publication 900-UM007D-EN-E - January 2011

5-74

Parameter Functions & Definitions

HB ON/OFF (900-TC8, 900-TC16)

Conditions of Use:

The controller hardware that supports the Heater

Burnout (HB), Heater Short (HS), and Heater Overcurrent (HO), Alarm 1
must be configured and the appropriate number of Current Transformers
(CT) to support the application are connected to the controller.

Function:

This parameter allows you to configure the operation of the Heater

Burnout Alarm (HBA).

Heater Burnout Latch (900-TC8, 900-TC16)

Conditions of Use:

The HB ON/OFF parameter must be configured to ON

and the controller hardware must support the Heater Burnout (HB), Heater
Short (HS), and heater overcurrent detection. Alarm 1 must also be configured
to ON. The appropriate number of Current Transformers (CT) to support the
application must be connected to the controller.

Function:

When this parameter is configured to ON, the heater burnout

alarm is held ON until one of the following reset conditions are satisfied:

• The Alarm Output is turned OFF when switching to the Initial Setting

function group, Communications Setting function group, Advanced
Setting function group, or Calibration function group, or

• Heater burnout detection is set to 0.0 A, or

• Controller power is cycled from ON to OFF.

• The latch is canceled by the PF key (900-TC8 only). PF Setting = LAT:

Alarm Latch Cancel.

• The latch is canceled by an event input. (Event Input Assignment 1 and

2 = LAT: Alarm Latch Cancel).

Table 5.CI

Selections

Default Selection

on: Alarm Enabled

off: Alarm Disabled

on