In-t, Tr-t, Tr-h – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 200

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-64

Parameter Adjustments & Application Considerations

EXAMPLE

Operating Procedure

The following procedure configures the Transfer Output Type as a SP with a
range (limit) of

−50…200.

Figure 4.137 — Operation function group

1. Press the O key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.138

2. Select the Transfer Output Type parameter by pressing the Key.

Figure 4.139

3. Press the U key to select sp (set point).

Figure 4.140

4. Select the Transfer Output Upper-Limit parameter by pressing the M

key.

Figure 4.141

C

25

100

PV/SP

in-t

5

Input type

tr-t

off

Transfer output
type

tr-t

sp

C

tr-h

1300

Transfer output
upper limit