Sero, Input error output – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 309

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-81

Related Parameters

• Operation/Adjustment Protection, Initial Setting/Communications

Protection, Setting Change Protection (Protect function group, page
5-1)

Input Error Output

Conditions of Use:

Alarm 1 must be assigned.

Function:

When this parameter is configured to ON, the output assigned to

the Alarm 1 output turns ON at an input error condition. Note, however, that
the Alarm 1 operation LED display does not light.

Note:

For details on input errors, refer to Error displays.

The Alarm 1 output is:

• the ORed output of Alarm 1, HB Burnout alarm, HS Alarm, heater

overcurrent alarm and the input error.

• turned OFF when controller operation is switched to the Initial Setting

function group, Communications Setting function group, Advanced
Setting function group, or Calibration function group, and when
controller power is cycled ON to OFF.

Related Parameter

• Input Error (Error Display, page 6-1)

Table 5.CT

Configurable Range

Units

Default Value

1…30

Seconds

3

Table 5.CU

Selections

Default Selection

on: Enabled

off: Disabled

off

sero