Publication 900-UM007D-EN-E - January 2011

4-60

Parameter Adjustments & Application Considerations

3. Select the PID ON/OFF parameter by pressing the U Key.

Figure 4.126

4. Select the Move to Advanced Setting parameter by pressing the M Key

5. Press the D Key to enter the password (-169), and move from the

Initial Setting function group to the Advanced Setting function group.

Figure 4.127

6. Select the Auto/Manual Select Addition parameter by pressing the

M

Key.

Figure 4.128

7. Use the

U

Key to set the parameter to ON.

Figure 4.129

8. Press the M Key to select the PF Setting parameter and confirm that it

is set to “A-M.” (“A-M” is the default setting.)

Figure 4.130

amov

0

Move to Advanced
Setting Group

init

off

Parameter
Initialization

amad

off

Auto/Manual
Select Addition

amad

on

pf

a-m