Set point 0 set point 1 set point 2 set point 3 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 261

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-33

Related Parameters

Refer to the Advanced Setting function group:

• Leakage Current 2 Monitor (page 5-14)
• HS Alarm Use, HS Alarm Latch, HS Alarm Hysteresis (page 5-88)

Set Point 0

Set Point 1

Set Point 2

Set Point 3

Conditions of Use:

The Number of Multi-SP Uses parameter must be

configured to either 1 or 2, and the Multi-SP Uses parameter must be
configured to ON.

Function:

These parameters allow you to configure multiple (up to 4) set

point values as long as the Multi-SP function is also configured.

For 900-TC8 or 900-TC16,

the configured values configured in these 4

parameters can be selected (loaded into the controller) by operating the keys
on the front panel or by event input.

Table 5.AJ

• While operating (RUN) if a change is made to a set point (SP 0, SP 1,

SP 2, or SP 3) it takes effect approximately 2 seconds after entering the
value, or upon depressing the

or

M

key.

• When using a temperature input, the decimal point position is

dependent on the selected sensor.

• When using an analog input, the decimal point position is dependent on

the setting of the Decimal Point position parameter.

Configurable Range

Units

Default Value

Set Point Lower-Limit to Set Point Upper-Limit

EU

0

sp-0

sp-1

sp-2

sp-3