If a shorter PV rate of change calculation period is configured, outputs for the
PV change rate alarm may repeatedly turn ON and OFF for a short period of
time. Therefore, it is recommended that the PV change rate alarm be used with
the alarm latch turned ON.

Figure 3.92

Heater Burnout Alarm
(HBA), Heater Short Alarm
(HSA), and Heater
Overcurrent Alarm (HOA)

HBA, HSA, and HOA Alarm Detection — 900-TC8 & 900-TC16 only

Heater burnout and heater overcurrent detection are executed by:

1.

measuring heater current with an optional current transformer (single
phase) or

2.

transformers (3 -phase) while the control output for heating is ON, and
HS detection is executed by measuring heater current while it is OFF.

For details, refer to the following table and figure below..

Note:

Heater burnout, heater short, and heater overcurrent detection cannot
be used with the control output for cooling.)

PV

Alarm value

Time

PV change width for PV rate
of change calculation period

Alarm function

OFF

ON

OFF

ON

0

Table 3.O

Parameter Name

Configurable
Range

Units

Default

PV Rate of Change Calculation Period 1...999

Sampling Cycle

4 (1 s)