Publication 900-UM007D-EN-E - January 2011

Parameter Functions & Definitions

5-25

AT Execute/Cancel

Conditions of Use:

The Bulletin 900-TC8, 900-TC16, or 900-TC32 must be

in operation (RUN), and the control method must be 2-PID control.

Function:

This parameter allows you to initiate (turn ON) the controller’s AT

(auto-tuning) function.

When you initiate auto-tuning, the optimum PID parameters (Proportional
Band, Integral Time, and Derivative Time) for the current set point during
program execution are automatically set by the controller forcibly changing the
manipulated variable to calculate the characteristics of the control target.

Table 5.AA

• Both 100% AT and 40% AT are supported for AT.

• Only 100% AT can be executed for heating and cooling control.

• For 900-TC8 and 900-TC16: This parameter will not be displayed

when either 100% or 40% AT execute/cancel is set to be executed using
an event input.

• This parameter is normally

off

. Press the

U

Key and select

at-2

or

at-1

to execute AT. AT cannot be executed when control is stopped or

during ON/OFF control.

• When AT execution ends, the parameter setting automatically returns to

off

.

Related Parameters

• Proportional Band, Integral Time, Derivative Time (Adjustment

function group, page 5-35)

• PID ON/OFF (Initial Setting function group, page 5-55)

Configurable Range

Default

OFF: AT Cancel

OFF

AT-2: 100% AT Execute

AT-1: 40% AT Execute

at