Parameter Functions & Definitions

Function:

This parameter allows you to configure the hysteresis (allowed

deviation from setting) for the operation of the Heater Short Alarm (HSA).

Related Parameter

• HS Alarm Use (Advanced Setting function group, page 5-88)

Loop Break Alarm (LBA) Detection Time

Conditions of Use:

Alarm 1 must be assigned. The Alarm Type must be set

to 12 (LBA).

Function:

This parameter allows you to enable or disable the LBA function

and set the detection time interval. To disable the LBA function, set it to 0.

Note:

For more details concerning the LBA Detection Time refer to
Section 4,

Loop Break Alarm on page 4-47.

Related Parameters

• Alarm 1 Type (Initial Setting function group, page 5-59)
• LBA Level (page 5-90), LBA Band (page 5-91) (Advanced Setting

function group)

Loop Break Alarm (LBA) Level

Conditions of Use:

Alarm 1 must be assigned. The Alarm Type must be set

to 12 (LBA). The LBA detection time must NOT be 0.

Table 5.DG

Configurable Range

Units

Default

0.1…50.0

A (Amps)

0.1

Table 5.DH

Configuration Range

Units

Default

0…9999

Seconds

0