Figure 3.9 — typical example 2, In-t, Cntl – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 81: Alt1, Al-1

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

Configuration & Basic Operation

3-11

Figure 3.9 — Typical Example 2

9

20

30

2

150

onof

pid

on

off

on

off

run
stop

Input type:

9 (T thermocouple,

200

°

C to 400

°

C)

Control method: PID control
PID constants found using
auto-tuning (AT).
Alarm type:

2 upper limit

Alarm value 1: 30

°

C

Set point:

150

°

C

Setup Procedure

Power ON

Initial Setting
function
group

Set input
specifications

Set control
specifications

Set alarm type

Adjustment
function
group

AT execution

(When PID
control is
selected)

Operation
function
group

Set alarm value

Start operation

Power ON

25

0

C

in-t

9

cntl

pid

st

off

cp

20

alt1

2

25

150

C

at

off

25

150

C

r-s

run

al-1

30

C

at

on

at

off

26

150

C

25

150

C

M

M

M

M

M

M

M

M

Operation
function group

PV/SP

Press the

O

key for

at least 3 s.

Control stops.

Initial Setting
function group

Use the

U

and

D

keys to

select the input
type.

Input type:

Use the

U

and

D

keys to select

PID control.

ON/OFF
control:

Use the

U

and

D

keys to set ST

to OFF.

To execute
ST:

PID

control:

To cancel
ST:

Check the
control period.

Control period
(heat)
(Unit: Seconds)

Check the
alarm type.

Alarm 1 type:

For PID, set

pid

.

When ON, self-tuning
operates.

It is recommended that 20 seconds
be set for a relay output and 2
seconds for an SSR voltage output.

Press the

O

key for

at least 1 s.

Operation
function group

Use the

U

and

D

keys to set

the SP to 150

°

C.

PV/SP:

Adjustment
function group

Execute AT.

To execute
AT:
To cancel
AT:

To execute AT (auto-tuning), select

on

: (AT execute), and to cancel AT,

select

off

: (AT cancel).

Press the

O

key

(for less than 1 s).

Press the

O

key

(for less than 1 s).

Control starts.

Operation
function group

Confirm that the
set point is
150

°

C.

PV/SP

Confirm that
control is
running.

Running
Stopped

Use the

U

and

D

keys to set

the alarm value
to 30

°

C.

Alarm
value 1

Start operation.

PV/SP
after AT is
stopped

The set point
flashes during
auto-tuning (AT)
execution.
After AT is
stopped

During AT
execution