Publication 900-UM007D-EN-E - January 2011

Parameter Adjustments & Application Considerations

4-57

EXAMPLE

Operating Procedure

Use the following procedure to set the manipulated variable in Manual mode.

Figure 4.111

1. Press the O key for at least 3 seconds to move from the Operation

function group to the Initial Setting function group.

Figure 4.112

2. Select the PID ON/OFF parameter by pressing the M key and select

PID mode.

Figure 4.113

3. Select the Move to Advanced Setting function group parameter by

pressing the

M key.

Figure 4.114

Press the

D key to enter the password (−169), and move from the Initial

Setting function group to the Advanced Setting function group.

Figure 4.115

C

25

100

PV/SP

in-t

5

Input type

cntl

pid

amov

0

Move to Advanced
Setting Function Group

init

off

Parameter
initialization