Parameter Adjustments & Application Considerations

4-85

Operating Procedure

This procedure sets the PF Setting parameter to PFDP, and the
Monitor/Setting Item 1 parameter to 7 (Alarm Value 1).

Figure 4.190 — Operation Function Group

1. Press the O Key for at least three seconds to move from the Operation

to the Initial Setting function group.

Figure 4.191

2. Select the Move to Advanced Setting function group parameter by

pressing the

M Key.

Figure 4.192

3. Press the D Key to enter the password (-169). It is possible to move to

the Advanced Setting function group by either pressing the

M Key or

waiting two seconds without pressing any key.

Figure 4.193

4. Press the M Key to select the PF Setting parameter.

Figure 4.194

C

25

100

PV/SP

in-t

5

Input Type

amov

-169

Move to Advanced
Setting Function Group

init

off

Parameter
Initialization

pf

a-m

PF Setting