In-t, Amov, Init – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 221

Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations
4-85
Operating Procedure
This procedure sets the PF Setting parameter to PFDP, and the
Monitor/Setting Item 1 parameter to 7 (Alarm Value 1).
Figure 4.190 — Operation Function Group
1. Press the O Key for at least three seconds to move from the Operation
to the Initial Setting function group.
Figure 4.191
2. Select the Move to Advanced Setting function group parameter by
pressing the
M Key.
Figure 4.192
3. Press the D Key to enter the password (-169). It is possible to move to
the Advanced Setting function group by either pressing the
M Key or
waiting two seconds without pressing any key.
Figure 4.193
4. Press the M Key to select the PF Setting parameter.
Figure 4.194
C
25
100
PV/SP
in-t
5
Input Type
amov
-169
Move to Advanced
Setting Function Group
init
off
Parameter
Initialization
pf
a-m
PF Setting