Publication 900-UM007D-EN-E -January 2011

C-18

Calibration

Checking Indication
Accuracy

• After calibrating input, make sure to check indication accuracy to make

sure that the Bulletin 900 Controller has been correctly calibrated.

• Operate the Bulletin 900 Controller in the PV/SP monitor mode.

• Check the indication accuracy at the Upper- and Lower-Limits and

mid-point.

Checking Accuracy of a Thermocouple or Non-Contact
Temperature Sensor

• Preparation: The following figure shows the required device

connection. Make sure that the Bulletin 900 Controller and cold
junction compensator are connected by a compensating conductor for
the thermocouple that is to be used during actual operation. For the
non-contact temperature sensor, connect a K thermocouple, and
configured the Input Type to the K thermocouple.

Figure C.36

Cold Junction Compensator

Input Power Supply

Compensation Conductor

900-TC8

1

2

19

20

-

+

STV

Cold Junction Compensator

Input Power Supply

Compensation Conductor

900-TC16

9

10

4

5

-

+

STV

Cold Junction Compensator

Input Power Supply

Compensation Conductor

900-TC32

1

2

11

12

-

+

STV

900-TC8

900-TC16

900-TC32