Setting the pf key – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 218

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-82

Parameter Adjustments & Application Considerations

8. Press the

M Key to select the MV Change Rate Limit parameter.

Figure 4.187

9. Use the

U Key to set the parameter to 5.0.

Figure 4.188

10. Press the

O Key to return to the Operation function group.

Figure 4.189

Setting the PF Key

PF Setting (Function Key)

Pressing the PF Key for at least one second executes the operation configured
in the PF Setting parameter (900-TC8 only).

The possible operations are outlined in the below table.

Table 4.AL

Set Value Symbol Operation

Function

OFF

off

Disabled

Does not operate as function key

RUN

run

RUN

Specifies RUN status

STOP

stop

STOP

Specifies STOP status

R-S

r-s

RUN/STOP reverse
operation

Specifies reversing the RUN/STOP
operation status

AT-2

at-2

100% AT
Execute/Cancel

Specifies reversing the 100% AT
Execute/Cancel status (see note 1)

AT-1

at-1

40% AT
Execute/Cancel

Specifies reversing the 40% AT
Execute/Cancel status

orl

0.0

MV
Change
Rate Limit

orl

5.0

MV
Change
Rate Limit

C

25

100

PV/SP