Setting the pf key – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 218

Publication 900-UM007D-EN-E - January 2011
4-82
Parameter Adjustments & Application Considerations
8. Press the
M Key to select the MV Change Rate Limit parameter.
Figure 4.187
9. Use the
U Key to set the parameter to 5.0.
Figure 4.188
10. Press the
O Key to return to the Operation function group.
Figure 4.189
Setting the PF Key
PF Setting (Function Key)
Pressing the PF Key for at least one second executes the operation configured
in the PF Setting parameter (900-TC8 only).
The possible operations are outlined in the below table.
Table 4.AL
Set Value Symbol Operation
Function
OFF
off
Disabled
Does not operate as function key
RUN
run
RUN
Specifies RUN status
STOP
stop
STOP
Specifies STOP status
R-S
r-s
RUN/STOP reverse
operation
Specifies reversing the RUN/STOP
operation status
AT-2
at-2
100% AT
Execute/Cancel
Specifies reversing the 100% AT
Execute/Cancel status (see note 1)
AT-1
at-1
40% AT
Execute/Cancel
Specifies reversing the 40% AT
Execute/Cancel status
orl
0.0
MV
Change
Rate Limit
orl
5.0
MV
Change
Rate Limit
C
25
100
PV/SP