Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 392

Advertising
background image

Publication 900-UM007D-EN-E -January 2011

C-14

Calibration

10. When the M Key is pressed, the status changes as shown to the left.

The data to be temporarily registered is not displayed if it is not
complete. Press the

U Key. The No. 2 display changes to yes. Release

the key and wait two seconds or press the

M Key. This stores the

temporarily registered calibration data to EEPROM.To cancel the
saving of temporarily registered calibration data to EEPROM, press the

M Key (while no is displayed in the No. 2 display) without pressing the

U Key.

11. The calibration mode is quit by turning the power OFF.

Figure C.25

Calibrating Analog Input
(e.g., 4…20 mA Analog
Input)

Calibrating an Analog Current Input (900-TC8 & 900-TC16)

In this example, calibration is shown for a Controller with an Analog current
Input (Input Type 0 or 1).

1. Connect the power supply.

2. Connect an STV and DMM to the current input terminals, as shown in

the following diagram.

Figure C.26

3. Turn the power ON.

4. Move to the calibration function group.

This starts the 30-minute aging timer. This timer provides an
approximate timer for aging. After 30 minutes have elapsed, the No. 2
display changes to 0. You can advance to the next step in this procedure
even if 0 is not displayed.

str

no

STV

DMM

+

9

10

4

5

Input Power Supply

900-TC16

900-TC8

STV

DMM

+

1

2

19

20

Input Power Supply