Parameter Functions & Definitions

5-77

AT Calculated Gain

AT Hysteresis

Limit Cycle MV Amplitude

Conditions of Use:

Control must be configured to 2-PID control. Normally

use the default values for these parameters

Function:

The AT Calculated Gain parameter sets the gain when PID values

are calculated using AT. When emphasizing response, decrease the set value.
When emphasizing stability, increase the set value. The AT Hysteresis
parameter sets the hysteresis for limit cycle operation during auto tuning when
switching ON and OFF. The Limit Cycle MV Amplitude parameter sets the
MV amplitude for limit cycle operation during auto tuning.

Note:

When temperature unit is °F, the default is 1.4.

Related Parameters

• AT execute/cancel (Adjustment function group, page 5-25)

Input Digital Filter

Function:

This parameter allows you to configure the time constant of the

controller’s input digital filter. Figure 5.12 shows the effect on the input data
after passing through the digital filter.

Table 5.CN

Parameter

Configuration Range

Units

Default

AT Calculated Gain

0.1...10.0

---

0.8

AT Hysteresis

Universal input:
0.1...999.9

° C or ° F

0.8 (see note)

Analog input 0.01...9.99

%FS

0.20

Limit Cycle MV Amplitude 5.0...50.0

%

20.0

at-g

at-h

lcma

inf