Publication 900-UM007D-EN-E -January 2011

C-8

Calibration

value is outside the specified range, the Number 2 display will flash and
the count value will NOT be temporarily registered.

6. Press the M key to set the Bulletin 900 Controller to the state below. Set

STV to –6 mV. Allow the count value on the No. 2 display to fully
stabilize, then press the

D key to temporarily register the calibration

setup. If the count value is outside the specified range, the Number 2
display will flash and the count value will NOT be temporarily
registered.

Figure C.9

7. Press the M Key. The display changes as shown above.. Set the STV to

700 mV.
Allow the count value on the No. 2 display to fully stabilize, then press
the

D Key to temporarily register the calibration settings. If this count

value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.

Figure C.10

8. Press the M Key. The display changes as shown on the left.Set the STV

to 400 mV. Allow the count value on the No. 2 display to fully stabilize,
then press the

D Key to temporarily register the calibration settings.

If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered

Figure C.11

9. When the M Key is pressed, the status changes as shown to the left.

Figure C.12

t

-

-6

2988

c700

-

ba13

c400

4

29be

bias

35b8