Parameter Functions & Definitions

5-13

Function:

This parameter measures the heater current from two CT inputs

used for detecting heater alarm conditions in 3-phase heaters and displays the
value on the controller.

• Heater burnout, heater short, and heater overcurrent conditions are not

detected if the Control Output (heating) ON time is 100 ms or less.

ffff

is displayed when 55.0 A is exceeded.

• If a heater burnout detection 2 or heater overcurrent detection 2 alarm

is output, the HA indicator will light and the No. 1 display for the heater
current 2 value monitor will flash.

Related Parameters

Refer to the Advanced Setting function group:

• Heater Burnout Detection 1, Heater Burnout Detection 2 (page 5-30)
• HB ON/OFF (page 5-30)
• Heater overcurrent detection 1, Heater overcurrent detection 2 (page

5-30)

• Heater overcurrent use (page 5-30)
• Error Displays

ct2

: (Chapter 6, page 6-5)

Leakage Current 1 Monitor
(900-TC8 &900-TC16)

Conditions of Use:

Heater Burnout (HBA), Heater Short (HSA), and Heater

Overcurrent (HOA) alarms must be supported. Alarm 1 must be assigned and
CT Number 1 wired to the controller. The HS Alarm Use parameter must be
set to ON.

Function:

This parameter measures the heater current from the Number 1

CT input used for detecting a short-circuit condition in single-phase heaters.

The heater current is measured and the value is displayed.

Table 5.N

Monitoring Range

Units

0.0...55.0

A (Amps)

lcr1