On/off counter reset, Ra 2 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 336

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

5-108

Parameter Functions & Definitions

count alarms to auxiliary outputs and to have them displayed on the screen.
This function is disabled when the set value is 0.

Related Parameter

• Control output 1 ON/OFF count monitor (Advanced Setting function

group, page 5-107)

Control Output 2 ON/OFF Count Alarm Set
Value (900-TC8, 900-TC16)

Conditions of Use:

Control output 2 must be supported. Relay or voltage

outputs (for driving SSR) must be used.

Function:

An ON/OFF count alarm occurs when the ON/OFF counter

exceeds the value set for this parameter. It is possible to assign ON/OFF
count alarms to auxiliary outputs and to have them displayed on the screen.
This function is disabled when the set value is 0.

Related Parameter

• Control output 2 ON/OFF count monitor (Advanced Setting function

group, page 5-107)

ON/OFF Counter Reset

Conditions of Use:

Control outputs 1 and 2 must be supported. Relay or

voltage outputs (for driving SSR) must used.

Table 5.EH

Configurable Range

Units

Default

0 to 9999

100 times

0

Table 5.EI

Configurable Range

Units

Default

0 to 9999

100 times

0

ra 2

rac