On/off counter reset, Ra 2 – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 336

Publication 900-UM007D-EN-E - January 2011
5-108
Parameter Functions & Definitions
count alarms to auxiliary outputs and to have them displayed on the screen.
This function is disabled when the set value is 0.
Related Parameter
• Control output 1 ON/OFF count monitor (Advanced Setting function
group, page 5-107)
Control Output 2 ON/OFF Count Alarm Set
Value (900-TC8, 900-TC16)
Conditions of Use:
Control output 2 must be supported. Relay or voltage
outputs (for driving SSR) must be used.
Function:
An ON/OFF count alarm occurs when the ON/OFF counter
exceeds the value set for this parameter. It is possible to assign ON/OFF
count alarms to auxiliary outputs and to have them displayed on the screen.
This function is disabled when the set value is 0.
Related Parameter
• Control output 2 ON/OFF count monitor (Advanced Setting function
group, page 5-107)
ON/OFF Counter Reset
Conditions of Use:
Control outputs 1 and 2 must be supported. Relay or
voltage outputs (for driving SSR) must used.
Table 5.EH
Configurable Range
Units
Default
0 to 9999
100 times
0
Table 5.EI
Configurable Range
Units
Default
0 to 9999
100 times
0
ra 2
rac