Executing the heating and cooling control mode, Overview – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual

Page 148

Advertising
background image

Publication 900-UM007D-EN-E - January 2011

4-12

Parameter Adjustments & Application Considerations

6. Select the decimal point position by pressing

M

.

Figure 4.24 — Press the

U or D key to set the parameter to 1.

Figure 4.25

7. To return to the Operation function group press the

key for at least

1 second.

Note: The newly configured value or parameter is loaded into controller

memory if you do NOT operate any key on the front panel for at least
2 seconds or by pressing the

or

M

key.

Executing the Heating and
Cooling Control Mode

Overview

Several forms/modes of heating, cooling, or heating and cooling control can
be used with Bulletin 900 controllers. The heating and cooling control mode
operates when

h-c

: heating and cooling is selected in the Standard/Heating

and Cooling parameter (Initial Setting function group). To assign the function
of your outputs and alarms based on the control mode use the Control Output
X Assignment and Alarm Y Assignment parameters in the Advanced Settings
function group. Refer to the table below

The following functions are assigned to outputs in the initial status.

dp

0

Decimal point

dp

1

Table 4.B — Output and Alarm Assignments

Parameter Name

Symbol

Initial Status

Control Output 1 Assignment

out1

Control output for heating

Control Output 2 Assignment (900-TC8 & 900-TC16 only)

out2

Not assigned

Auxiliary Output 1 Assignment

sub1

Alarm 1

Auxiliary Output 2 Assignment (900-TC8 & 900-TC16 only)

sub2

Alarm 2

Auxiliary Output 3 Assignment (900-TC8 only)

sub3

Alarm 3

Each output assignment is automatically initialized as shown below when the control module is changed.