Wt-b mv-s, Wait band, Mv at stop – Rockwell Automation 900-TC32 Digital Temperature Controllers, Series B User Manual
Page 268

Publication 900-UM007D-EN-E - January 2011
5-40
Parameter Functions & Definitions
Wait Band
Conditions of Use:
The Program Pattern parameter must NOT be set to
OFF.
Function:
This parameter enables you to configure the stable band within
which the soak time is measured for the simple program function.
➊ Set NONE as the unit for Controllers with 0…50 Millivolt Inputs.
Related Parameters
• Program Start, Soak Time Remain (Operation function group, page
5-15)
• Soak Time (Adjustment function group, page 5-39)
• Program Pattern (Initial Setting function group, page 5-57)
• Soak Time Unit (Advanced Setting function group, page 5-96)
MV at Stop
Conditions of Use:
The control method must be configured for 2-PID
control. The MV at Stop and Error Addition parameter must be configured to
ON.
Function:
This parameter allows you to configure the amount the MV
(process output) is OPEN/ON when the RUN/STOP status changes from
RUN to STOP.
Table 5.AS
Controller Type
Configurable
Range
Units
Default
With Thermocouple or Resistance
Thermometer (RTD)
OFF or
0.1…999.9
°C or °F ➊
Off
With Analog Inputs
OFF or
0.01…99.99
%FS
Table 5.AT
Configurable Range
Units
Default
−5.0…105.0 for standard control
−105.0…105.0 (heating/cooling control)
%
0.0
wt-b
mv-s