Figure 3.104 — Heater Burnout Detection

EXAMPLE

Using Two 200V AC, 2 kW Heaters, V Connecting Lines

Figure 3.105 — V Connecting Lines

The heater burnout current when there is a burnout at the common is as
follows:
Heater burnout detection current = (10 + 5) / 2

≈ 7.5 [A]

The heater burnout current when there is a burnout at the load is as follows:
Heater burnout detection current = (10 + 0) / 2

≈ 5 [A]

To enable detection in either case, use 7.5 A as the heater burnout detection
current.

CT

CT

200 V

200 V

5 A

5 A

200 V

Load

Load

CT

CT

200 V

200 V

5 A

5 A

200 V

Load

Load

Burnout

Burnout

Load (such as a heater)

Load (such as a heater)

Load

Load

To CT input

To CT input

Burnout

Current when there is a burnout = 10 A

Ч

(1/

3)

Ч

(

3/2) = 5 A

Current when there is a burnout = 10 A

Ч

(1/

3)

Ч

(

3/2) = 5 A

To CT Controller input

To CT Controller input

CT

CT

Load

200 V

10 A

10 A

17.3 A

200 V

200 V

Load

Normal

To CT input

To CT Controller input